To calculate dehumidification load we have to calculate evaporation from indoor pool surface ,moisture from outside ventilation air and moisture from occupants .
1-from ASHRAE handbook can take evaporation rate from activity factor (AF) depend on application residential or hotel or, ..etc
2- evaporation rate factor (ERF) depend on swimming pool water temperature and air temperature (lb/hr.sq ft)
3- determine pool area in (sq .ft)
4- then can calculate evaporation rate (lb/hr) = ERF lb/hr. sq ft X AF X pool area
5- ventilation moisture = [CFM oa x (grains oa - grains return)]/
6- recommended ACH 4-8 for outside air7- for one person calculate btu/ hr latent heat load and calculate enthalpy h(lb/hr).
Download Also: International Swimming Pool and Spa Code and swimming pool design spreadsheet
Swimming Pools Dehumidification Calculation Sheet
Factors are used in calculating evaporation from the swimming pool:- Water temperature
- Air temperature
- Air relative humidity
- Pool area
- Saturation vapor pressure taken at surface water temperature
- Saturation pressure at dew point
- Level of activity in the pool