Download NFPA 780 lightning protection calculator, it is also called lightning risk assessment. We will provide you with lightning protection system design calculation (excel sheet). Risk management in accordance with IEC 62305-2 (EN 62305-2) includes a risk analysis to determine whether lightning protection is required, this excel sheet will help you in this mission.
Download also: Capacitor Size Calculator for Power Factor improvement (XLS)
Lightning Protection Risk Assessment |
Download Lightning Protection Calculator Excel Sheet (Risk Assessment)
Lightning risk assessment:
Risk assessment for lightning protection is important as not all buildings need lightning protection system. The above spreadsheet will help you determine Lighting Protection System (LPS) should be installed or not.lightning protection rod |
Risk Assessment formula:
There are various parameters must be taken in the design of Lightning Protection:
Nd =(Ng) x (Ae) x (C1) x 10 ^-6
Nc =(1.5 x 10^ -3) /((C2)(C3)(C4)(C5))
where:
Nd Yearly expected lightning strike frequency to the structure
Nc Tolerable lightning strike frequency to the structure
Ng Yearly average flash density in the region (fl/km2/year)
Ae Equivalent collective area of the structure (km2)
C1 Environmental coefficient
C2 Structure Coefficient
C3 Structure Contents Coefficient
C4 Structure Occupancy Coefficient
C5 Lightning Consequence Coefficient
Risk Calculation:
if Nd ≤ Nc Hence, LPS May Be Optional
Nd > Nc Hence, LPS Should Be Installed
We introduced to you the free lightning protection risk assessment calculator excel sheet which depends on the NFPA 780 code (National Fire Protection Agency).