A fire pump is a part of a fire protection system’s water supply. It is important to know that a fire pump does not create water, it takes water that is given to it from a water supply such as underground water tank and increases the pressure (energy) of the water. 


Head of fire pump = Hs + Hr + HLF + HLP

Hs: Static Head
Hr: Residual Head
HLF: Friction Loss Head
Friction Loss Head =  Friction Loss in Pipes + Friction Loss in Fittings

All these calculations of fire pump head are performed in the following excel sheet.

Download also: NFPA Tables In One Excel Sheet, Fire Sprinklers and Fire Pump Tables





Fire Pump Head Calculation  Excel Sheet